Easy setup and simple operation The TTSIM-1A Sensor Interface Module monitors up to 150 meters (500 feet) of TraceTek sensing cable. When liquid is detected, the TTSIM-1A unit indicates the leak with an LED, and switches a relay to provide local voltage-free contact closure. The TTSIM-1A can also communicate to a host monitoring system such as a TraceTek TTDM-128 or directly to a PLC or other host system using standard protocols. The low cost of the TTSIM-1A makes it economical to build very robust systems with many small independent sensing cable segments. No field calibration is required.
 
The TTSIM-1A can be used as a stand-alone leak detection alarm unit, or in networks with other TraceTek TTSIM, TT-NRM or TTDM-128 modules. The TTSIM-1A can be configured using a Microsoft Windows™ based PC, or a TraceTek TTDM-128 network master module.

1、Design features
—— Voltage-free contacts for alarm signaling.
—— LEDs to indicate power, leak, cable trouble, and commu-

2、nication status.
—— Simple twisted pair serial RS-485 communications up to
—— 1200 meters (4000 feet) with automatic protocol selection

3、(MODBUS, Opto 22 and Metasys).
—— Available for 24, 120 or 230 Vac 50/60 Hz or 12 or 24 Vdc

4、power supply.
—— Each TTSIM-1A unit has a unique address assigned with

5、software – no switches.
—— Relay software selectable for normally energized or nor-

6、mally de-energized operation
—— DIN rail mounted for easy installation.
—— Enclosures available for stand-alone indoor or outdoor

General features
Sensor compatibility:      All TraceTek sensor cables and point sensors or contact closure devices
Maximum length of sensing cable:      150 m (500 ft)
Precision:      0.5% of sensor length ± 0.6 m (2 ft)
 
Environmental ratings
Storage temperature:      18°C to 60°C (0°F to 140°F)
Operating temperature:      0°C to 50°C (32°F to 122°F)
Humidity:      5% to 95% non-condensing

Power requirements
TTSIM-1A:      22 to 26 Vac, 50/60 Hz, 3 W (SELV level for Europe)
TTSIM-1A-120:      92 to 132 Vac, 50/60 Hz, 3 W
TTSIM-1A-230:      216 to 253 Vac, 50/60 Hz, 3 W
TTSIM-1A-12VDC:     12 Vdc +/– 10%, 2 W
TTSIM-1A-24VDC:     24 Vdc +/– 10%, 2 W
Wire sizes:     #22 AWG to #14 AWG (0.5 to 2.5 mm2)

Ordering information                           
Catalog numbe r  ——  Part number —— Description
TTSIM-1A —————   P000000046 —— 24 Vac TTSIM-1A
TTSIM-1A-12 0 ——— P000000047 —— 120 Vac TTSIM-1A
TTSIM-1A-230 ———  P000000048 —— 230 Vac TTSIM-1A
TTSIM-1A-12VDC —— P000000899 —— 12 Vdc TTSIM-1A

TTSIM-1A-24VDC —— P000000906 —— 24 Vdc TTSIM-1A 


Serial interface

Network configuration RS-485 two wire network, 9600 baud, addressable from 1 to 127
Communication protocol Modbus®, OptoMux™ or Johnson Controls Metasys™

Relay contacts 
Type —— Form C (SPDT)
Action —— Software selectable; normally energized or normally de-energized; alarm on leak; leak or fault; or leak, fault or service
Rating —— 2 Amps maximum, 250 Vac or 30 Vdc(30 V SELV level max for Europe)

Approvals and Certifications
TraceTek sensors in Class I, Division 2, A, B, C, D Hazardous Locations (Zone2 in Europe). If protected by an agency approved zener barrier, TraceTek sensors in Class I, Division 1, Groups A, B, C, D Hazardous Locations (Zones 0 and 1 in Europe). Contact Pentair Thermal Building Solutions to select proper zener barrier.Only AC versions are UL listed and VDE Certified. For DC models use a Listed Class 2 Power Supply.